1.In outgoing feeders control cables are crossing around the terminals.This will obstruct the termination of power cables.
2.Incomer CT sec.cables entering from outgoing feeder transformer it will obstruct the termination of outgoing cable.
3.Cable Screen Earthing connected on both ends it should be one end.
4.There is no R/Y/B color coding for CT secondary cables,PT & MV cables,it should be IEC standard.The present color coding is for ‘R’ phase- yellow,‘Y’ phase- Green & ‘B’ phase- Red marking has been done.
5.12KV insulators are used to connect metering PT cables on 13.8KV side it should be at least 15KV class.
6.PT‘s missing in the metering cubicle.
7.In control cubicle no access for Aux.Transformer maintenance.
8.No specification available for Aux.transformer.
9.No emergency PB provided outside the container in the event of emergency to actuate and trip.
10.There is no metering for outgoing feeders each time to submit total generation,both Trafo incomer meter energy reading has to be summated.
我不行了,句子看不懂
关于中国注意的点做变压器容器1.In外出的饲养者控制电缆在终端附近横渡的.这将阻碍电缆的终止.2.Incomer CT秒.进入从外出的饲养者变压器的缆绳它将阻碍外出的缆绳的终止.3.Cable在两个末端连接的屏幕接地它应该是一个末端4.There是没有R/Y/B颜色编码为CT次要缆绳,PT 5.12KV绝缘体在13.8KV它应该是15KV至少类的边用于连接测量的PT缆绳.6.PT错过在测量的小卧室的`s.7.In控制台室没有通入为辅助.变压器维护.8.No规格可利用为辅助.变压器.9.No紧急情况的铅在容器之外提供在紧急状态情形下开动和绊倒.